K0916 K916: Have a battery powered remote alarm panel in a location accessible by operating personnel.
F

Emergency Generator Annunciator Panel Malfunction

St Mary's Center For Rehabilitation & HealthcareCherry Hill, New Jersey Survey Completed on 12-06-2024

Summary

The facility failed to ensure that the emergency generator annunciator was fully functional and operating in normal mode, as required by NFPA 99: 2012 Edition, Section 6.4.1.1.17 and 6.4.1.1.17.5. During an observation at 11:32 AM, it was noted that the generator annunciator panel's test lamp button did not work when activated. Although the generator produced a green light on the annunciator panel indicating it was running, no other alarm condition lights functioned at the time of observation. This deficiency was identified for the only generator annunciator panel in the facility and had the potential to affect all residents. The findings were communicated to the relevant personnel at the Life Safety Code exit conference.

Plan Of Correction

K0916 Level F Completion Date: 1/15/2025 Corrective Action: The generator was inspected and found to be functioning as designed and a new annunciator control board ordered for Generator Annunciator Panel. ID Other Residents: All residents within the facility have the potential to be affected. Systemic Change: In-service Annunciator Panel Monitoring and Resident Safety to the Maintenance Department by the Maintenance Director completed by 12/20/2024. Monitoring: Audit - Annunciator Panel will be completed on the following schedule: every quarter x 3 quarters by the Maintenance Director/Designee. Results of the audits will be brought to QA/QAPI on a quarterly basis xs 3 quarters.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0916 citations in Ohio
Nonfunctional Generator Alarm Annunciators at Nurses’ Stations
F
K0916 K916: Have a battery powered remote alarm panel in a location accessible by operating personnel.
Short Summary

Surveyors observed that generator annunciator panels at two nurses’ stations had no functional indicator lights and had their key switches in the off position, contrary to NFPA 99 requirements for essential electrical systems. An MD reported that he only becomes aware of generator problems by physically checking the generator displays, and testing showed the key controlled an audible signal when the generators were running, confirming the annunciators were not being used to indicate emergency power source alarm conditions.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙