K0293 K293: Have properly located and lighted "Exit" signs.
F

Deficient Exit Signage Near Kitchen

Hartwyck At Oak TreeEdison, New Jersey Survey Completed on 12-20-2024

Summary

The facility failed to ensure proper exit signage in accordance with NFPA 101:2012 Edition, Sections 19.2.10.1 and 7.10. During an observation at 11:00 AM, it was noted that there was no directional exit sign indicating the direction of travel to the nearest exit when exiting the smoke barrier doors near the kitchen. This deficiency was confirmed through an interview with the U.S. FOIA present at the time of the observation. The lack of appropriate signage had the potential to affect all residents, as the direction of travel to the nearest exit was not apparent.

Plan Of Correction

1. All residents have the potential to be affected by this deficient Life Safety Code. A directional exit sign was installed near the kitchen on 12/31/24 by [R]. The sign is wall mounted, is internally illuminated, and clearly indicates the direction of travel to the nearest exit. A complete facility-wide inspection of all exit signs was conducted on 12/31/24 to ensure no other areas are lacking proper signage. 2. The Maintenance Director will modify the scheduled maintenance calendar to include a quarterly Exit Sign inspection to be conducted to ensure all facility exit signs are in the proper location and functioning. 3. The maintenance director will review the quarterly exit sign inspection reports with the administrator quarterly and submit to the QAA committee quarterly for 1 year.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0293 citations
Failure to Maintain Continuous Illumination of Exit Sign
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Surveyors found that an exit sign above the door leading to grade from the stairtower near the Elevator Lobby was not illuminated as required. This lack of illumination was confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Illuminated Exit Signage
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

A deficiency was identified when an exit sign near a resident room in one smoke compartment was found to be unilluminated, as confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Monthly Exit Sign Inspections
C
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Surveyors found that the facility did not have documentation to verify that monthly visual inspections of exit signs were completed over the past year. This was confirmed by the DON and Director of Maintenance during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exit Signs Not Illuminated on Emergency Power
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Exit signs in the older section of the facility failed to illuminate when tested for battery back-up, indicating they were not transferring to emergency power as required. The maintenance director believed the signs were working, but testing and observation confirmed the deficiency, which could affect 50 occupants during a power outage.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exit Sign with Battery Backup Failed to Illuminate During Test
D
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

An exit sign with a battery backup near the kitchen corridor failed to illuminate when tested, as observed during a facility tour and confirmed by the Environmental Supervisor. This deficiency affected 15 residents and one smoke compartment, indicating the exit sign was not maintained in accordance with NFPA 101 requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Exit Signage and Egress Configuration
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Exit and directional signs were not properly displayed or configured, with the emergency exit sign outside the Saginaw Room Dining space set up incorrectly. This left the North side of the facility without an emergency exit from resident spaces, and the exit configuration did not match the emergency placards in the corridors. These issues were confirmed by the maintenance director during the survey.

Fine: $30,740
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙