Failure to Maintain Fire Resistance Rating in Common Walls

Willowbrooke Court-southamptonSouthampton, Pennsylvania Survey Completed on 01-28-2025

Summary

The facility failed to maintain the fire resistance rating of common walls, which is a requirement for sections of health care facilities classified as other occupancies. During an observation, it was noted that there was an unsealed penetration around data wires above the common wall doors separating Willowbrooke Court and the Independent Living Unit. This deficiency was identified on one of the two levels of the facility. The issue was confirmed during an exit interview with the Administrator and Maintenance Director.

Plan Of Correction

Preparation and/or execution of this plan of correction does not constitute an admission or agreement by the provider of the truth of the facts alleged or conclusions set forth in the statement of deficiencies. The plan of correction is prepared and/or executed solely because it is required by the provisions of State and Federal Law. The plan of corrections represents the community's credible allegation of compliance. Maintenance technician sealed the identified penetrations around the data wires above the common wall doors separating Willowbrooke Court and Independent Living Unit using UL system WL-3423 on 1/29/2025. The Maintenance Department will be in-serviced by 2/14/2025 the Director of Property Management/ Designee on maintaining the fire resistance rating of common walls. All fire door separations in Willowbrooke Court were audited by 2/12/2025 by maintenance technician for penetrations and maintenance of fire rating. The Director of Property Management or designee will conduct random weekly audits x4 weeks to check fire resistance rating of common walls, affecting one of two levels. All findings will be reported to QAPI Committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0131 citations
Failure to Maintain Fire-Resistant Door Barriers
E
K0131
Short Summary

Surveyors identified that fire-rated doors in the basement elevator lobby area had multiple penetrations and extensive damage, compromising the required fire resistance rating for common wall separations. Facility leadership confirmed these deficiencies during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Building Separation
E
K0131
Short Summary

The facility failed to maintain proper building separation in sections classified as other occupancies. An observation revealed that the doorway to Country House, between skilled nursing and assisted living, lacked a 1 1/2 hour fire-resistant door. This deficiency was confirmed during an exit interview with the Administrator and the Director of Maintenance, acknowledging the lack of complete two-hour fire-resistant separation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance Rating in Facility
D
K0131
Short Summary

The facility failed to maintain a two-hour fire resistance rating between the main building and the west wing due to a door that did not latch properly, affecting one of the smoke compartments. This deficiency was confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance in Common Wall Separations
E
K0131
Short Summary

The facility failed to maintain fire resistance in common wall separations as certain fire-rated doors did not positively bottom latch. Observations revealed that the double doors at Tony's Café and a level fire door in the basement, both separating different components, failed to latch properly. This was confirmed during an exit interview with the Facility Administrator and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Resistance Deficiency in Facility
E
K0131
Short Summary

The facility failed to maintain the fire resistance rating of common wall fire separations, affecting one of three levels. The rated double doors near the basement loading dock did not fully close and positively latch when tested. This was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Fire Separation in Facility Occupancies
F
K0131
Short Summary

The facility failed to maintain proper fire separation between Healthcare and Residential occupancies, with unprotected wire penetrations and missing brick sections compromising the two-hour fire resistance rating. These deficiencies were confirmed during an inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙