K0916 K916: Have a battery powered remote alarm panel in a location accessible by operating personnel.
F

Emergency Generator Annunciator Panel Deficiency

Hartwyck At Oak TreeEdison, New Jersey Survey Completed on 12-20-2024

Summary

The facility failed to ensure compliance with NFPA 99 standards regarding the emergency generator's remote annunciator. During an observation, it was noted that the remote annunciator panel for the emergency generator was not functioning properly at the nurse's station on the second floor. Specifically, the panel lacked a means to indicate it was receiving power and did not have a lamp test switch to verify the operation of all alarm lamps. This deficiency was confirmed through an interview with the U.S. FOIA representative present during the survey. The issue was communicated to the facility's representative during the Life Safety Code exit conference.

Plan Of Correction

1. All residents have the potential to be affected by this deficient Life Safety Code. A qualified contractor, NJ Ex Order 26.4(b)(1), was contacted and came to assess the generator on 1/6/25 and will repair/replace the remote annunciator panel to include a means to show that it is receiving power and a lamp test switch(es) to test the operation of all alarm lamps. This work was completed by NJ Ex Order 26.4(b)(1) on 2/11/2025. 2. The Maintenance Director added a monthly annunciator panel test to the generator maintenance schedule. 3. The Maintenance Director will review the generator maintenance and inspection reports monthly to ensure that the required testing was completed timely. The results of this review will be submitted to the administrator and to the QAPI committee monthly and to the QA committee quarterly ongoing.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0916 citations in Ohio
Nonfunctional Generator Alarm Annunciators at Nurses’ Stations
F
K0916 K916: Have a battery powered remote alarm panel in a location accessible by operating personnel.
Short Summary

Surveyors observed that generator annunciator panels at two nurses’ stations had no functional indicator lights and had their key switches in the off position, contrary to NFPA 99 requirements for essential electrical systems. An MD reported that he only becomes aware of generator problems by physically checking the generator displays, and testing showed the key controlled an audible signal when the generators were running, confirming the annunciators were not being used to indicate emergency power source alarm conditions.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙