K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
F

Failure to Maintain and Test Fire Alarm System and Batteries

Riverbank Post-acuteRiverbank, California Survey Completed on 03-18-2025

Summary

The facility failed to maintain its Fire Alarm System (FAS) in accordance with NFPA 101, NFPA 70, and NFPA 72 requirements. During a tour and document review, surveyors observed a trouble signal on the Fire Alarm Control Panel (FACP) at Nurse Station A, which was initially attributed by staff to a smoke detector being accidentally hit by equipment in a resident room. Upon resetting the FACP, the panel began displaying a cycle of trouble signals for various devices throughout the facility, with a new trouble signal appearing approximately every two seconds. A monitoring report confirmed this ongoing cycle of trouble signals, and the FAS vendor indicated that a technician would be needed to diagnose the issue. Testing of the water flow device, two smoke detectors, and a tamper switch showed that notification devices activated and signals were received by the monitoring company. Additionally, the facility failed to conduct required annual testing of the FACP batteries, specifically the discharge and charger tests. The dates of the last tests were unknown, and no records of these tests were provided when requested by surveyors. Staff confirmed the lack of testing and indicated they would follow up with their vendor, but no documentation was submitted by the deadline. These deficiencies affected all residents and smoke compartments in the facility.

Plan Of Correction

K 345 - Fire Alarm System Testing and Maintenance How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: The facility immediately contacted its fire alarm system vendor to diagnose and address the ongoing trouble signals. The vendor completed necessary repairs on 4/4/25, and all alarms are now fully operational. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken: All residents have the potential to be affected. On 4/4/25, the facility performed a comprehensive assessment of all fire alarm system components to identify any additional deficiencies. No other deficiencies were noted. What measures will be put into place or what systemic changes the facility will make to ensure that the deficient practice does not recur: The EVS Director will perform a monthly check for 3 months then semi-annually to ensure semi-annual and annual fire alarm testing is completed on time. The EVS Director was trained by the Administrator on 4/9/25 on the importance of fire alarm testing and functionality. How the facility plans to monitor its performance to make sure that solutions are sustained. The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system: The EVS Director will perform a monthly check for 3 months then semi-annually to ensure semi-annual and annual fire alarm testing is completed on time. Results will be reviewed in the QAPI meetings for ongoing compliance oversight. Date of Compliance 4/18/25

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations in Ohio
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Fire Alarm System per NFPA Requirements
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and document its fire alarm system in accordance with NFPA 101 and NFPA 72, potentially affecting all residents. The only annual fire alarm record provided was a single page without a device list, and there was no documentation of required semi-annual visual inspections or sensitivity testing of devices. During the tour, surveyors observed multiple fire alarm breakers in various electrical panels that were not marked in red, not secured from unauthorized access, and in one case left in the off position, with panel labeling insufficient to identify the presence of a fire alarm breaker. These findings were confirmed with the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙