K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
D

Unsealed Penetration in Smoke Barrier Wall

Riverbank Post-acuteRiverbank, California Survey Completed on 03-18-2025

Summary

During a facility tour and staff interview, surveyors observed that the smoke barrier wall above the fire doors near Room 12 had an unsealed penetration measuring approximately two inches in diameter, which contained a metal conduit. This condition was confirmed by a staff member, who acknowledged that he had not yet inspected the smoke barrier walls. The unsealed penetration compromised the smoke integrity of the barrier wall, which is required to have a minimum 1/2-hour fire resistance rating according to NFPA 101, Life Safety Code, 2012 Edition. This deficiency affected 27 out of 92 residents and one of six smoke compartments in the facility. The report does not mention any specific medical history or condition of the residents involved, but it directly states that the unsealed penetration could result in the spread of smoke in the event of a fire. The deficiency was identified through direct observation and staff confirmation during the survey.

Plan Of Correction

K 372 - Smoke Barrier Construction How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: • The identified penetration was sealed using fire-rated caulking and fire-resistant materials in accordance with NFPA 101 and NFPA 8.5.6.2 standards. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken: • No other residents have the potential to be affected. The penetration was limited to its specified smoke compartment. • A comprehensive review of all smoke barrier walls was conducted to identify any other unsealed penetrations. No other issues were found. What measures will be put into place or what systemic changes the facility will make to ensure that the deficient practice does not recur: • A quarterly smoke barrier inspection protocol has been implemented, with documentation maintained for compliance review. • The EVS Director was trained by the administrator on the importance of proper inspection and sealing of smoke barrier penetrations. How the facility plans to monitor its performance to make sure that solutions are sustained: The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system; • Results will be reviewed in the QAPI meetings for ongoing compliance oversight. Date of Compliance 4/18/25

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations in Ohio
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Barrier Integrity per NFPA 101
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found multiple penetrations in smoke barriers sealed with non-fire-rated materials and one unsealed pipe, compromising the required fire and smoke resistance in several corridors and the attic. Maintenance leadership confirmed uncertainty about the materials used, and these deficiencies had the potential to affect all 39 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙