K0363 K363: Install corridor and hallway doors that block smoke.
D

Corridor Door Failed to Latch Due to Maintenance Issue

Ceres Postacute CareCeres, California Survey Completed on 05-19-2025

Summary

During a facility tour and interview with the Maintenance Director, surveyors observed that the corridor door to Room 5 failed to latch when tested. The door was found to be rubbing against the door frame, which prevented it from properly securing. The Maintenance Director indicated that the issue was likely related to the door hinges and mentioned that staff usually checked on the doors. This deficiency affected 25 out of 46 residents in one of three smoke compartments. The report specifically notes that the corridor doors did not maintain the required latching function, as mandated by NFPA 101 and related regulations, which is necessary to resist the passage of smoke and fire. No additional details about the medical history or condition of the residents involved were provided in the report.

Plan Of Correction

How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: Maintenance staff on the same day after the first failed test addressed the issue with Rm. 5 door not latching by adjusting the hinges and striker plate, retested, and door successfully latched. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken: All residents have the potential to be affected by this deficient practice. No residents were found to be affected by this practice. What measures will be put into place or what systemic changes in the facility will make to ensure that the deficient practice does not recur: Rounds will be done monthly by maintenance and the proper setting of the doors will be logged and the administrator will review the rounds and develop a log. How the facility plans to monitor its performance to make sure that solutions are sustained: The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The Administrator shall report the outcome of the checks/inspections to the Quality Assurance and Assessment Committee (QA&A) during its monthly meeting. If determined that the facility has accomplished the objectives in the plan of correction as aforementioned and the results are successful, then the facility shall consider the matter resolved. The QA&A Committee shall continue to review until such time that the deficiency has been proven to be resolved for 3 consecutive months and/or as advised by the QA&A Committee. Date of Completion of Corrective Action: 05/19/2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0363 citations in Ohio
Failure of Corridor Doors to Latch as Required by NFPA 101
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two corridor doors would not latch despite multiple attempts, and a staff member was unaware of the regulatory requirements. This deficiency had the potential to affect 17 residents, as the doors did not meet NFPA 101 standards for smoke resistance and positive latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliant Corridor Door Hold-Open Device
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found a corridor door held open by an unapproved chain and magnet, which interfered with the door's latching mechanism and did not meet NFPA requirements for smoke resistance and positive latching, potentially affecting 13 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙