K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
F

Failure to Complete Required Generator Load Bank Testing and Documentation

Urbana Health & Rehabilitation CenterUrbana, Ohio Survey Completed on 06-05-2025

Summary

The facility failed to maintain its diesel generator in accordance with NFPA 110-2010 requirements. During a review of the life safety documentation, it was found that the last four-hour load bank test of the generator had not been completed within the required 36-month interval, with the most recent test occurring several years prior. Additionally, the monthly test records did not document the engine hours as required, instead only noting the start and end times of the test. These findings were confirmed by the Maintenance Director, who was unaware of the specific requirements for generator testing and documentation. This deficiency had the potential to affect all 46 residents in the facility, as the generator is a critical component of the essential electrical system. The lack of proper testing and documentation means the facility could not ensure the generator's reliability in supplying emergency power within the required timeframe, as outlined by NFPA 110 standards. No specific resident medical histories or conditions were mentioned in relation to this deficiency.

Plan Of Correction

K918 Urbana Health and Rehab wishes to point out to any person who reviews this document that we do not necessarily agree with the citations with which we were cited. However, the law requires us to prepare a plan of correction for the citations regardless of whether we agree with them or not. Thus, we have prepared such a plan as noted below. Please note though, that this plan does not constitute an admission that the citations are either legally or factually correct. This plan of correction is not meant to establish any standard of care, contract, obligation, or position, and Urbana Health and Rehab reserves all rights to raise all possible contentions and defenses in any civil or criminal action or proceeding. Please accept 07/30/25 as the facility's allegation of compliance date. The facility failed to ensure that the 4-hour 36-month load test was completed on the generator and written record of maintenance and testing was logged incorrectly. Step 1: Facility Administrator obtained the 4-hour bank test documentation from 6/9/2023. Step 2: NHA audited the generator testing log for the time meter reading—start and end—ensuring that it would include hours of the engine, not the test start and end time. Maintenance Director corrected log entry for the month of July 2025. Step 3: NHA educated Maintenance Director on the correct way to log generator testing entries 7/15/25.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0918 citations in Ohio
Failure to Maintain and Document Required Generator Testing and Safety Features
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to maintain required documentation showing that its three generators were tested monthly and inspected and tested annually in accordance with NFPA 99 and NFPA 110. Despite multiple requests, no records of these tests or inspections were provided. During the facility tour, surveyors also observed that none of the three generators were equipped with remote manual stop buttons, and this was confirmed by the Maintenance Director. This deficient practice had the potential to affect all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙