K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
E

Hazardous Area Door Failed to Self-Close and Latch

Mission Point Nursing & Physical Rehabilitation CeGrand Rapids, Michigan Survey Completed on 06-25-2025

Summary

A deficiency was identified when the A Hall Resident Care Supply room door was observed not to self-close to a positive latch as required by Life Safety Code (LSC) 8.7.1.3. This observation was made during a facility inspection and confirmed in an interview with a maintenance staff member. The lack of a self-closing, positively latching door in this hazardous area means the area was not properly protected as required for spaces containing combustible or hazardous materials, as outlined in LSC 19.3.2.1. The deficiency was specifically noted in relation to the protection of hazardous areas, which is necessary to prevent the spread of fire and smoke within the facility.

Plan Of Correction

Element #1: A Hall Resident Care Supply room door self-closer has been adjusted. The A Hall Resident Care Supply room door was checked to ensure the door self-closed to a positive latch. Element #2: This deficient practice has the potential to affect 15 occupants of the facility in the event of a fire not being contained to the hazardous area. Hazardous area doors in the facility have been checked and verified that they self-close to a positive latch. Doors that did not self-close to a positive latch were fixed at the time of the audit. Element #3: Nursing Home Administrator/designee has completed re-education with the Environmental Service Director on the Fire and Smoke Doors policy by the completion date. Element #4: Environmental Services Director/designee will complete audits on hazardous area doors to ensure they self-close to a positive latch. Audits will be completed weekly for four weeks and then monthly thereafter until substantial compliance is sustained. Results of the audits will be reported to facility QAPI committee for review and recommendations. This plan of correction will be monitored at the routine Quality Assurance (QAPI) meeting until such a time it is identified by the committee that sustained substantial compliance has been achieved. The Nursing Home Administrator is responsible for attaining and maintaining compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0321 citations in Ohio
Failure to Maintain Self-Closing Doors for Multiple Hazardous Storage Areas
F
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that multiple hazardous storage areas, including a closet near medical records, a beauty salon used to store chemical cases, a supply room in one nursing station, a room leading to a smoking area, a housekeeping room near therapy, and a lobby storage room, lacked required self-closing or automatic-closing doors. These conditions did not comply with NFPA 101 requirements for hazardous area enclosure and had the potential to affect all residents and staff in an emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙