K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
E

Failure to Address Failed Fire Dampers in HVAC System

Sanatoga CenterPottstown, Pennsylvania Survey Completed on 08-06-2025

Summary

The facility failed to maintain its Heating, Ventilating, and Air Conditioning (HVAC) equipment as required. During a document review, it was found that the April 2025 Fire Damper Inspection Report identified two failed dampers. At the time of the survey, there was no evidence available to show that corrective action had been taken to address these failed dampers. This deficiency was confirmed during the exit interview with the Administrator and Maintenance Director. No information about residents or their medical conditions was included in the report.

Plan Of Correction

Vendor scheduled for damper repair. The Maintenance Director will be reeducated by the NHA/Designee on K0521 with focus on the importance of ensuring fire damper inspections are being completed and checking to ensure building is in compliance. Monthly audits to be completed x 4 to ensure valid fire damper inspection in place. Maintenance director/Designee will report findings of inspection at QAPI meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0521 citations in Ohio
Lack of Required Inspection and Testing Documentation for Fire Dampers
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not maintain required documentation showing that fire dampers had been inspected and tested in accordance with NFPA 101, NFPA 90A, and NFPA 80 standards. During record review, no inspection or testing records were produced despite multiple requests, even though fire dampers were observed throughout the building. The Maintenance Director confirmed that the documentation was not available, and this deficiency had the potential to affect all 69 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙