K0923 K923: Have proper medical gas storage and administration areas.
D

Failure to Post Required 'No Smoking' Signage in Oxygen Cylinder Storage Area

Cottage Crest Post AcuteNorwalk, California Survey Completed on 05-28-2025

Summary

Surveyors observed that a full H-sized oxygen cylinder was stored in the beauty salon, which is used as a temporary storage area when the salon is not in use. During the observation, it was noted that there was no 'No Smoking' sign posted in the area where the oxygen cylinder was stored, nor at the exterior entrances of the facility. The Chief Medical Officer (CMO) confirmed during the interview that the sign was missing and acknowledged the temporary storage practice in the salon. A review of the facility's policy and procedure titled 'Oxygen Safety' indicated that precautionary signs readable from five feet should be maintained on the door or gate where oxygen is used or stored. The lack of required signage in the area where the oxygen cylinder was stored was found to be out of compliance with NFPA 99, Health Care Facilities Code, 2012 Edition, Section 11.3.4. This deficiency was identified in one of five smoke compartments during the survey.

Plan Of Correction

Date of compliance: June 20, 2025 K923 Gas Equipment - Cylinder and Container Storage CFR(s): NFPA101 Corrective Action Initiated for those resident(s) found to have been affected by deficient practice Upon notification of the deficient practice on 05/28/2025, the MS posted "No Smoking signs" on the exterior of areas of the Oxygen Room and the Beauty Shop on 05/28/2025. (Exhibit #4 & Exhibit #5) How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken. There was no other trend identified and no other residents were affected by this deficient practice. Measures put into place or systematic changes the facility will make to ensure the deficient practice does not occur On 05/28/2025, the ADM provided an in-service/re-education to MS regarding policies and procedures on Oxygen Safety, ensuring that there are "No Smoking" signs in areas where oxygen cylinders were stored. Monitoring for the effectiveness and the sustainability of the corrective action put into place to correct the issue identified. An observational audit of rooms with oxygen use will be done once a month by MS for 3 months and kept in a log. A summary of this deficient practice will be brought to the monthly QA meeting for 3 months by MS for evaluation of the plan effectiveness and sustainability. Date of compliance: June 20, 2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0923 citations
Failure to Maintain Required Oxygen Cylinder Storage and Secured Storage Room
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen storage requirements were not maintained when a freestanding oxygen cylinder was observed unsecured in a third-floor room and the C-Hall oxygen storage room door failed to close and latch due to a coordinator malfunction. The Maintenance Director confirmed these oxygen storage deficiencies during the survey exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Oxygen Cylinders Near Combustibles
F
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors observed that more than 12 "E" oxygen cylinders (18 total) were stored in a sprinkler room within five feet of combustible materials, contrary to NFPA 99 requirements for gas equipment cylinder storage. The Maintenance Director confirmed this storage practice during the survey. This noncompliance with NFPA 99 sections 11.3.1–11.3.3 was cited as a deficiency affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Room Cautionary Signage
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that an oxygen storage room on the second floor lacked the required precautionary signage stating, "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING," as mandated for gas cylinder storage areas. This deficiency was confirmed by facility leadership during the initial survey and again during a subsequent revisit, when the same room was still missing the required sign.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Signage in Crash Cart Rooms
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders were stored in crash cart rooms in two separate cores without the required precautionary signage on the doors indicating oxidizing gas storage and no smoking. Observations in two smoke compartments showed oxygen cylinders present in the 3 East and 2 East core crash cart rooms, yet the doors lacked the mandated "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING" signage. The facility administrator and maintenance leadership confirmed that the proper oxygen storage signs were not posted on these doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Near Combustibles and Electrical Receptacles
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders stored within first- and second-floor nurses' stations were placed less than five feet from electrical receptacles and combustible materials, in violation of NFPA 99/101 requirements for separation of oxidizing gases from combustibles and ignition sources. The Administrator and Maintenance Director confirmed during interview that the cylinders were improperly stored in proximity to these combustible and ignition sources.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage and Security of Gas Cylinders
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that gas cylinders were improperly stored and unsecured, with 38 cylinders in an outside storage room lacking the required oxidizing gas signage and with full and empty cylinders comingled, and an additional 25 cylinders stored adjacent to this area without any means to prevent unauthorized access. During an interview, the Maintenance Director acknowledged the issues and reported being unaware of the specific NFPA 99 storage requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙