Bathroom Ventilation Systems Not Operational
Summary
The facility failed to ensure that ventilation systems were operational in residents' bathrooms in rooms 33, 34, 36, 39, 40, and 41 to prevent odors. During observations on 3/30/26 and again on 3/31/26, the bathroom fans were running but did not draw a 1-ply square of toilet paper, showing the ventilation was not functioning properly. In interview, the Maintenance Director stated that the bathroom ventilations were only checked monthly when cleaning the vents and that the fan was considered working if it could be heard running; the Maintenance Man stated he was not aware the bathroom ventilation systems were not working and confirmed the fans came on but did not pull the toilet paper. The Maintenance Director confirmed the ventilation system was not working, and the Administrator confirmed the bathroom ventilation was not working and that there was no policy and procedures regarding the ventilation system.