K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
F

Deficient Emergency Power System Maintenance and Documentation

Willowbrook ManorFlint, Michigan Survey Completed on 06-24-2025

Summary

The facility failed to ensure that its generators and associated emergency power systems were maintained and tested in accordance with NFPA 110, NFPA 99, NFPA 111, and NFPA 70 standards. During an observation, it was found that the automatic transfer switch number 2 for the equipment branch was not functioning, as indicated by the absence of display and indicator lights. The maintenance director confirmed that this issue had persisted since February or March, and that the generator company had not yet responded to address the malfunction. Despite the malfunction, the facility continued to have lights and power during outages, but the non-functioning transfer switch could limit available resources during a power loss. Additionally, a review of facility records revealed that there was no documentation available to verify that the back-up emergency generator had been serviced annually or that the required annual load bank test had been conducted. The maintenance director stated that the generator company had recently visited but had not yet provided any paperwork. The lack of documentation means that the facility could be unaware of potential generator issues, which may result in generator failure during a power outage. These findings were confirmed through interviews with the maintenance director at the time of observation and record review.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0918 citations in Ohio
Failure to Maintain and Document Required Generator Testing and Safety Features
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to maintain required documentation showing that its three generators were tested monthly and inspected and tested annually in accordance with NFPA 99 and NFPA 110. Despite multiple requests, no records of these tests or inspections were provided. During the facility tour, surveyors also observed that none of the three generators were equipped with remote manual stop buttons, and this was confirmed by the Maintenance Director. This deficient practice had the potential to affect all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Complete Required Generator Load Bank Testing and Documentation
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

The facility did not complete the required four-hour load bank test of its diesel generator within the mandated 36-month period and failed to properly document engine hours during monthly tests, as confirmed by the Maintenance Director. This lapse affected the reliability of the essential electrical system for all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

99.5% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 64 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙